Damper related error

Lossnay Heat Recovery Ventilation — Error Code

Back to results
3602

Damper related error

Unit: Remote Controller Category: Lossnay Heat Recovery Ventilation
Unit Type
Remote Controller
Fault Point

1. Damper board operation is not correct

2. Connectors for the damper unit are not correctly connected

3. The switch (SW5-10) setting is incorrect

How to Fix
  1. 1)Remove the rod, and check whether the damper board can be moved manually
  2. 2)Check the connection of the lead wire connectors and the circuit connector
  3. 3)Check the switch (SW5-10) setting
  4. 4)LGH-15 to 100 types : OFF
  5. 5)LGH-150 and 200 types : ON