6607
No ACK error *ACK : Acknowledgement signal from other communicating devices No answer error (M-NET communication error)
Unit Type
Remote Controller
Fault Point
1. Power is not supplied to Lossnay
2. Lossnay address was changed
3. Multiple transmission cables are wired using multi core cable
4. Transmission cable is not securely connected
5. The length of the transmission cable wiring is longer than specified (longer than maximum extension 200 m, longer than 500 m between ends)
How to Fix
- 1)Check the power supply to Lossnay
- 2)Check the Lossnay address
- 3)Using suitable cables, wire the transmission cables so that they are separated from one another
- 4)Check the transmission cable connection
- 5)Check the length of the transmission cable wiring
Additional Info
when using M-NET
Remark
when using M-NET