6801
PZ-60DR-E communication error
Unit Type
Remote Controller
Fault Point
1. When using multiple Lossnay units, the Main/Sub setting has not been made for the second unit and following units
2. Multiple transmission cables are wired using multi core cables
3. Transmission cable and power cable are too close
4. Transmission cable is not securely connected
5. The length of the transmission cable wiring is longer than specified (longer than 500 m)
How to Fix
- 1)Turn off the main power and set the Main/Sub selection switch (SW1)(set the first unit to "Main" and the second and following units to "Sub")
- 2)Using suitable cables, wire the transmission cables so that they are separated from one another
- 3)Wire the transmission cable at least 5 cm away from the power supply cable
- 4)Check the transmission cable connection
- 5)Check the length of the transmission cable wiring
Additional Info
when using M-NET
Remark
when using M-NET