Lossnay Heat Recovery Ventilation — Green Light Blinking (Times)

Back to results
Outdoor: 3 times

Damper related error

Unit: Indoor Category: Lossnay Heat Recovery Ventilation
Unit Type
Indoor
Fault Point

1. Damper board operation is not correct

2. Connectors for the damper unit are not correctly connected

3. The switch (SW5-10) setting is incorrect

How to Fix
  1. 1)Remove the rod, and check whether the damper board can be moved manually
  2. 2)Check the connection of the lead wire connectors and the circuit connector
  3. 3)Check the switch (SW5-10) setting
  4. 4)LGH-15 to 100 types : OFF
  5. 5)LGH-150 and 200 types : ON
Additional Info
-
Remark
-