Refrigerant overcharge

City Multi VRF System — Error Code

Back to results
1500

Refrigerant overcharge

Category: City Multi VRF System
Primary Error Code
1600
Primary Error Detail Code
-
Error Code Description
<p>Refrigerant overcharge</p>
Searched Device
Outdoor
Fault Point

1.Overcharged refrigerant.

2.Thermistor input circuit failure on the control board.

3.Faulty mounting of thermistor. (TH15)

4.Outdoor unit LEV1/LEV2 malfunction.

5.Problems with indoor unit LEV. (malfunction, LEV leakage)

6.Installation of the twinning-pipe kit (on a model with multiple outdoor units)

How to Fix
  1. 1)Evaluating and Adjusting Refrigerant Charge.
  2. 2)Check the temperature and pressure readings on the sensor that are displayed on the LED monitor.
  3. 3)Check the temperature and pressure readings on the thermistor that are displayed on the LED monitor.
  4. 4)The valve opening changes according to the number of pulses.
  5. 5)4.1) Connections between the outdoor control board and LEV1. (outdoor expansion valve)
  6. 6)4.2) Pulse signal output and valve operation.
  7. 7)4.3) LEV valve closing and opening operation.
  8. 8)Malfunction:
  9. 9)Refer to the Service Handbook of the indoor unit.
  10. 10)LEV leakage:
  11. 11)Check the LEV on the stopped indoor unit in the cooling mode for refrigerant leak.
  12. 12)Check that the twinning-pipe kit is installed in accordance with the instructions provided in the installation manual.