1500
Refrigerant overcharge
Primary Error Code
1600
Primary Error Detail Code
-
Error Code Description
<p>Refrigerant overcharge</p>
Searched Device
Outdoor
Fault Point
1.Overcharged refrigerant.
2.Thermistor input circuit failure on the control board.
3.Faulty mounting of thermistor. (TH15)
4.Outdoor unit LEV1/LEV2 malfunction.
5.Problems with indoor unit LEV. (malfunction, LEV leakage)
6.Installation of the twinning-pipe kit (on a model with multiple outdoor units)
How to Fix
- 1)Evaluating and Adjusting Refrigerant Charge.
- 2)Check the temperature and pressure readings on the sensor that are displayed on the LED monitor.
- 3)Check the temperature and pressure readings on the thermistor that are displayed on the LED monitor.
- 4)The valve opening changes according to the number of pulses.
- 5)4.1) Connections between the outdoor control board and LEV1. (outdoor expansion valve)
- 6)4.2) Pulse signal output and valve operation.
- 7)4.3) LEV valve closing and opening operation.
- 8)Malfunction:
- 9)Refer to the Service Handbook of the indoor unit.
- 10)LEV leakage:
- 11)Check the LEV on the stopped indoor unit in the cooling mode for refrigerant leak.
- 12)Check that the twinning-pipe kit is installed in accordance with the instructions provided in the installation manual.