Skip to main content

Drain sensor (Thd) fault.

City Multi VRF System — Error Code

Back to results
2503

Drain sensor (Thd) fault.

Category: City Multi VRF System
Primary Error Code
-
Primary Error Detail Code
-
Error Code Description
<p>Drain sensor (Thd) fault.</p>
Searched Device
Indoor, Lossnay
Fault Point

1. Faulty connector (CN31) insertion.

2. Broken or semi-broken thermistor wire.

3. Thermistor failure.

4. Indoor unit control board (error detection circuit) failure.

How to Fix
  1. 1)Check for connector connection failure.
  2. 2)Reinsert the connector, restart the operation, and check for proper operation.
  3. 3)Check for a broken thermistor wire.
  4. 4)Check the resistance of the thermistor.
  5. 5)0°C[32 °F]:6.0 kΩ
  6. 6)10°C[50 °F]:3.9 kΩ
  7. 7)20°C[68°F]:2.6 kΩ
  8. 8)30°C[86°F]:1.8 kΩ
  9. 9)40°C[104 °F]:1.3 kΩ
  10. 10)Replace the indoor unit control board if the problem recurs when the unit is operated with the No.-1 and No.-2 pins on the drain sensor connector (CN31) being short-circuited.
  11. 11)If the above item checks out OK, there are no problems with the drain sensor.
  12. 12)Turn off the power and turn it back on.
Additional Info
-
Remark
-

Still having issues?

Our service team is ready to help you resolve this error.