Indoor unit fan operation error.

City Multi VRF System — Error Code

Back to results
4109

Indoor unit fan operation error.

Category: City Multi VRF System
Primary Error Code
-
Primary Error Detail Code
-
Error Code Description
<p>Indoor unit fan operation error.</p>
Searched Device
Indoor
Fault Point

1. Auxiliary relay (X13) fault.

2. Connector (CN28) is disconnected.

3. Blown fuse.

4. Motor error (thermistor error inside the motor).

How to Fix
  1. 1)The coil or the wiring of the auxiliary relay connected to CN28 is faulty.
  2. 2)Check the connector for proper connection.
  3. 3)Check the fuse on the control circuit board.
  4. 4)Check the unit fan for proper operation in the test run mode.
  5. 5)If no problems are found with items 1 through 3 above and the fan does not operate,
  6. 6)replace the motor.
Additional Info
-
Remark
-

Still having issues?

Our service team is ready to help you resolve this error.