Skip to main content

Function setting error.

City Multi VRF System — Error Code

Back to results
4121

Function setting error.

Category: City Multi VRF System
Primary Error Code
4171
Primary Error Detail Code
-
Error Code Description
<p>Function setting error.</p>
Searched Device
Outdoor
Fault Point

1. Dip switch setting error on the control board.

2. Connector connection error on the control board.

3. Control board failure.

How to Fix
  1. 1)Check the SW6-1 setting on the control board.
  2. 2)Check that nothing is connected to the connector CNAF on the control board.
  3. 3)Replace the control board if no problems are found with the two items above.