Skip to main content

Heatsink overheat protection. (Detail Code 125)

City Multi VRF System — Error Code

Back to results
4230

Heatsink overheat protection. (Detail Code 125)

Category: City Multi VRF System
Primary Error Code
4330
Primary Error Detail Code
-
Error Code Description
<p>Heatsink overheat protection. (Detail Code 125)</p>
Searched Device
Outdoor
Fault Point

the heat sink temperature (THHS) remains at or above 105°C [221°F] is detected.

How to Fix
  1. 1)Fan board failure.
  2. 2)1.1) Checking the Fan Board Error Detection Circuit at No Load.
  3. 3)1.2) Checking the Fan Inverter for Damage at No Load.
  4. 4)1.3) Checking the Fan Inverter for Damage with Load.
  5. 5)Outdoor unit fan failure.
  6. 6)2.1) Check the outdoor unit fan operation. If any problem is found with the fan operation.
  7. 7)2.2) Cecking the Fan Motor for Ground Fault and Coil Resistance Problems.
  8. 8)Check that the heat sink cooling air passage is not blocked.
  9. 9)Check for proper installation of the INV board IGBT. (Check for proper installation of the IGBT heatsink.)
  10. 10)Check the THHS sensor reading on the LED monitor.
  11. 11)→If an abnormal value appears, replace the INV board.
Additional Info
-
Remark
-

Still having issues?

Our service team is ready to help you resolve this error.