Skip to main content

Serial communication error/Panel communication error

City Multi VRF System — Error Code

Back to results
0403

Serial communication error/Panel communication error

Category: City Multi VRF System
Primary Error Code
4300, 4305, 4306
Primary Error Detail Code
1, 5, 6
Error Code Description
<p>Serial communication error/Panel communication error</p>
Searched Device
Indoor, Outdoor
Fault Point

(1) Incorrect switch setting on the indoor unit circuit

board

(2) Power wire that connects the circuit board on

the indoor unit and the circuit board on the

cleaning unit is loose.

(3) Communication wire that connects the circuit

board on the indoor unit and the circuit board

on the cleaning unit is loose.

(4) Panel transceiver circuit fault (cleaning unit)

(5) Panel transceiver circuit fault (indoor unit)

(6) Electrical interference on the cleaning unit's

communication cable

How to Fix
  1. 1)(1) Check SW3-3 on the indoor unit circuit board Set SW3-3 to ON only when connecting an auto filter cleaning unit. (2) Check the LED1 (cleaning unit circuit board (microcomputer power)). Lit: Power is supplied properly. Unlit: Check for loose or
  2. 2)disconnected power wire between the indoor unit circuit board (CNAC) and the cleaning unit circuit board (CN3A). (3,4,5,6) Check the LED4 (cleaning unit circuit board (communication)). Blinking: Normal communication Unlit: Check for loose or disconnected
  3. 3)communication wire between the indoor unit circuit board (CN3G) and the cleaning unit circuit board (CN3G). If the LED blinks at irregular intervals (normally blinks at 0.5-second intervals), electrical interference is suspected. Check the items above,
  4. 4)turn the power off, and turn the power back on. If the error persists, replace either the cleaning unit circuit board or the indoor unit circuit board.
Additional Info
-
Remark
-

Still having issues?