1102
Discharge temperature fault
Primary Error Code
1202
Primary Error Detail Code
-
Error Code Description
<p>Discharge temperature fault</p>
Searched Device
Outdoor
Fault Point
(1) Gas leak, gas shortage
(2) Overload operation
(3) LEV failure on the indoor unit
(4) Outdoor unit LEV1 actuation failure
Outdoor unit LEV2 actuation failure
(5) Closed refrigerant service valve
(6) Outdoor fan (including fan parts) failure, motor failure, or fan controller malfunction
Rise in discharge temp. by low pressure drawing for (3) - (6).
(7) Gas leak between low and high pressures (4-way valve failure, Compressor failure, Solenoid valve (SV1a) failure)
(8) Thermistor failure (TH4)
(9) Input circuit failure on the controller board thermistor
How to Fix
- 1)(1) Evaluating and Adjusting Refrigerant Charge
- 2)(2) Check operating conditions and operation status of indoor/
- 3)outdoor units.
- 4)(3), (4) Perform a cooling operation to check the operation.
- 5)Cooling: Indoor unit LEV, LEV1, LEV2
- 6)Refer to the following page(s). Troubleshooting LEV Problems
- 7)(5) Confirm that the refrigerant service valve is fully open.
- 8)(6) Check the fan on the outdoor unit.
- 9)Troubleshooting Outdoor Unit Fan Problems
- 10)(7) Perform a cooling operation and check the operation.
- 11)(8) Error Codes [5102, 5103, 5104, 5106, 5107]
- 12)(9) Check the inlet air temperature on the LED monitor.
Additional Info
-
Remark
-