Light Blinking Error Results (7 results)

# Light Blinking (Times) Type Description / Cause Solution Remark
1 1 Indoor

Communication circuit section error

1. Controller where error originally occurred is defective

2. Lossnay circuit board is defective

1. Check the controller where the error occurred. 2. Replace the circuit board

View details

when using M-NET

2 2 Indoor

Communication circuit section error

1. Controller where error originally occurred is defective

2. Lossnay circuit board is defective

1. Check the controller where the error occurred. 2. Replace the circuit board

View details

when using M-NET

3 3 Indoor

Communication circuit section error

1. Controller where error originally occurred is defective

2. Lossnay circuit board is defective

1. Check the controller where the error occurred. 2. Replace the circuit board

View details

when using M-NET

4 4 Indoor

Communication circuit section error

1. Controller where error originally occurred is defective

2. Lossnay circuit board is defective

1. Check the controller where the error occurred. 2. Replace the circuit board

View details

when using M-NET

5 5 Indoor

Transmission cable error

1. Power is not supplied to the same transmission cable from two or more power supply units

2. The power supply unit is connected to the TB3 side of the power supply expansion unit

3. The power supply unit is connected to the indoor and outdoor transmission cables

Adjust the wiring of the power supply unit

View details

when using M-NET

6 6 Indoor

Multiple address error

There is another unit with the same address setting

Check the addresses of devices in the system

View details

when using M-NET

7 8 Indoor

No ACK error

*ACK : Acknowledgement signal from other communicating devices

No answer error (M-NET communication error)

1. Power is not supplied to Lossnay

2. Lossnay address was changed

3. Multiple transmission cables are wired using multi core cable

4. Transmission cable is not securely connected

5. The length of the transmission cable wiring is longer than specified (longer than maximum extension 200 m, longer than 500 m between ends)

1. Check the power supply to Lossnay. 2. Check the Lossnay address. 3. Using suitable cables, wire the transmission cables so that they are separated from one another. 4. Check the transmission cable connection. 5. Check the length of the transmission cable wiring

View details

when using M-NET