Error Code Results (14 results)

# Error Code Type Description / Cause Solution Remark
1 0900 Remote Controller

Lossnay trial operation

Trial operation switch on the Lossnay circuit board (SW2-1) is set to ON

Check the trial operation switch

View details

-

2 3126 Remote Controller

External device error

When the TM3 ⑥,⑦ output setting switch (SW5-6) is ON, the following conditions are applied

・OA temperature is still -10°C or lower, 60 minutes after the output started

・OA temperature is 15°C or higher within 15 minutes after the output started

・OA temperature is 70°C or higher

1. When external devices are connected, check the external devices. 2. When external devices are not connected, check the TM3 ⑥,⑦ output setting switch (SW5-6)

View details

-

3 3602 Remote Controller

Damper related error

1. Damper board operation is not correct

2. Connectors for the damper unit are not correctly connected

3. The switch (SW5-10) setting is incorrect

1. Remove the rod, and check whether the damper board can be moved manually. 2. Check the connection of the lead wire connectors and the circuit connector. 3. Check the switch (SW5-10) setting. LGH-15 to 100 types : OFF. LGH-150 and 200 types : ON

View details

-

4 4116 Remote Controller

Fan motor operation drive error

1. The Lossnay fan does not stop due to a breakdown of the fan motor operation drive of the circuit board

2. Fan motor error

1. Check and replace the circuit board. 2. Check and replace the fan motor

View details

*LGH-150 and 200 types do not display errors

5 5101 Remote Controller

OA thermistor related error

Connectors for the thermistor are not correctly connected

Check the connection of the lead wire connectors and the circuit connectors

View details

-

6 5102 Remote Controller

RA thermistor related error

Connectors for the thermistor are not correctly connected

Check the connection of the lead wire connectors and the circuit connectors

View details

-

7 6600 Remote Controller

Multiple address error

There is another unit with the same address setting

Check the addresses of devices in the system

View details

when using M-NET

8 6602 Remote Controller

Communication circuit section error

1. Controller where error originally occurred is defective

2. Lossnay circuit board is defective

1. Check the controller where the error occurred. 2. Replace the circuit board

View details

when using M-NET

9 6603 Remote Controller

Transmission cable error

1. Power is not supplied to the same transmission cable from two or more power supply units

2. The power supply unit is connected to the TB3 side of the power supply expansion unit

3. The power supply unit is connected to the indoor and outdoor transmission cables

Adjust the wiring of the power supply unit

View details

-

10 6604 Remote Controller

Communication circuit section error

1. Controller where error originally occurred is defective

2. Lossnay circuit board is defective

1. Check the controller where the error occurred. 2. Replace the circuit board

View details

when using M-NET

11 6607 Remote Controller

No ACK error

*ACK : Acknowledgement signal from other communicating devices

No answer error (M-NET communication error)

1. Power is not supplied to Lossnay

2. Lossnay address was changed

3. Multiple transmission cables are wired using multi core cable

4. Transmission cable is not securely connected

5. The length of the transmission cable wiring is longer than specified (longer than maximum extension 200 m, longer than 500 m between ends)

1. Check the power supply to Lossnay. 2. Check the Lossnay address. 3. Using suitable cables, wire the transmission cables so that they are separated from one another. 4. Check the transmission cable connection. 5. Check the length of the transmission cable wiring

View details

when using M-NET

12 6801 Remote Controller

PZ-60DR-E communication error

1. When using multiple Lossnay units, the Main/Sub setting has not been made for the second unit and following units

2. Multiple transmission cables are wired using multi core cables

3. Transmission cable and power cable are too close

4. Transmission cable is not securely connected

5. The length of the transmission cable wiring is longer than specified (longer than 500 m)

1. Turn off the main power and set the Main/Sub selection switch (SW1)(set the first unit to "Main" and the second and following units to "Sub"). 2. Using suitable cables, wire the transmission cables so that they are separated from one another. 3. Wire the transmission cable at least 5 cm away from the power supply cable. 4. Check the transmission cable connection. 5. Check the length of the transmission cable wiring

View details

when using M-NET

13 6202 Remote Controller

Remote controller error

The remote controller has broken down

Replace the remote controller

View details

when not using M-NET

14 6608 Remote Controller

Lossnay communication error

1. When using multiple Lossnay units, the Main/Sub setting has not been made for the second unit and following units

2. Multiple transmission cables are wired using multi core cables

3. Transmission cable and power cable are too close

4. Transmission cable is not securely connected

5. The length of the transmission cable wiring is longer than specified (longer than 500 m)

1. Turn off the main power supply and set the Main/Sub selection switch (SW1)(first unit to "Main", second and following units to "Sub"). 2. Using suitable cables, wire the transmission cables so that they are separated from one another. 3. Wire the transmission cable at least 5 cm away from the power supply cable. 4. Check the transmission cable connection. 5. Check the length of the transmission cable wiring

View details

when not using M-NET LC